QYW-3 Series Multifunctional Transformer Protection Device
The QYW-3 series multi-function transformer protectors areintegrated dedicated protective relays developed specifically forfully-sealed oil-immersed transformers. They integrate gasprotection, overpressure protection, visual oil level monitoring withbuilt-in output contacts, and visual oil temperature monitoringequipped with dual-channel output contacts.
Boasting a wide range of applicable scenarios, the devices can be matched with oil-immersed power transformers,oil-immersed reactors, oil-immersed power capacitors and otheroil-filled electrical equipment. They serve as the standard safetyprotection assemblies for fully-sealed distribution transformers andbox-type substations.
Technical Features
Reference Standards IEC 60076-22-1 、 EN 50216-3
Item Parameter Description / Technical Index
IEC 60529/GB/T 4208-2017 Protection Class — IP56
IEC 62262/GB/T 20138-2023 Impact Resistance — IK10
Max. Relative Pressure — +3 Bar
Ambient Temperature Range — -40℃ < T < +70℃
Max. Oil Temperature — +120℃
Pressure Adjustment Range — 100 ~ 500 mbar
DEGUANG ELECTRICITY
Alarm Temperature Adjustment Range — +30℃ ~ 120℃
Trip Temperature Adjustment Range — +30℃ ~ 120℃
Fixed Trip Threshold for Gas & Oil Level — Trip when light gas volume exceeds
Climatic Conditions IEC60721-3-4 — 4K26
Special Climatic Conditions IEC60721-3-4 — 4Z2+4Z4+4Z14
Mechanically Active Substances IEC60721-3-4 — 4S13
Gas / oil level switch
240V 50/60Hz — 1 — Cosφ>0.5 — 2000 — 1000
24-48VDC — 1 — L/R<40ms — 2000 — 1000
220VDC — 0.1 — L/R<40ms — 2000 — 1000
Dielectric Withstand Voltage:
Dielectric Strength of Contacts / Rated Short-time Withstand Voltage
Between Contacts — 2.5 kV
Contacts to Earth — 1 kV