YSF20-50T,80T,125T Series Pressure Relief Device
YSF20-50T,80T,125T is mainly suitable for pressure relief inside the oil tank of large oil immersed power transformers, power capacitors, reactors and other equipment when the pressure exceeds the limit. In addition to the conventional electrical alarm signal, a computer electrical alarm signal function can also be added to achieve dual electrical signal output, and each can be independently led out. Users can choose according to their needs when ordering products.
1. Installation position: on the oil tank cap, on the raised seat, or on the upper side wall of the oil tank.
2. Environmental requirements: -30 ℃ to+70 ℃(can be customized according to user needs to support up to -45 ℃ to+70 ℃); Work environment requirements:- 30℃~+115℃(customizable according to user needs, can support up to -45 ℃~+115 ℃).
3. Relative humidity: not exceeding 95% at+20 ℃.
4. Protection level: IP56(Customizable according to user requirements). Scope of application: Altitude 0~4000m.
5. Power frequency withstand voltage: normally open contact 2000V/min, normally closed contact or single pole double throw contact: phase to phase 1000V/min, ground 2000V/min.
6. Insulation performance: normally open contact 2500V, 1000M Ω, normally closed contact or single pole double throw contact: phase to phase 1000V, 500M Ω, ground 2500V, 1000M Ω.
Outline and installation dimension diagram
1. The fuel injection diameter is Φ 80mm with electrical signal, and the pressure relief valve is connected by bolts as shown in Figure 2;